Inactive
Notice ID:36C26224C0320
The VA MEDICAL CENTER Building 8 ACC South Basement Level in ceiling sewage lines are corroded to the point of failure, pipe is open to atmosphere in multiple areas. Potential health risk to patients ...
The VA MEDICAL CENTER Building 8 ACC South Basement Level in ceiling sewage lines are corroded to the point of failure, pipe is open to atmosphere in multiple areas. Potential health risk to patients and staff replacement required. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 1. 2. Stress lab A0528 hallway and A0528A Room A0523, A0524, Pet/Central A0517 Break room A0527 Staff TLT A0407, A0526 Nuke Med A0514, A0515, A0510 hallway Sub wait A0512 Mechanical room A0800 Room A0506, A0504, A0615, A6018A Hot lab A0512B, AC0504, AC0500 Will prep areas for demo with plastic each night. All visual pitted/cracked Cast-iron pipe and fittings is to be remove from ceiling and dispose . 3. 4. Will install new Epoxy coated cast-iron pipe and fittings in existing hangers. This includes replacing up to 400-500 feet of 6 and 4inch main line with 2 - 3 inch branch lines above grid ceiling in ACC South. 5. Areas where access is not available we will perform a sewer lining where needed up to (30) 3'' stacks in walls and up to 80 ft of Horizontal piping. 6. All work will done after hours or on weekends to keep shut down to minimal.