H228--New Diesel powered generator maintenance Base Plus Four White City VAMC

Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14)
Notice ID:36C26026Q0706

The contractor will provide testing and exercise services for four diesel-powered emergency power supply (EPS) installations at the VA Southern Oregon Rehabilitation Center and Clinics (VA SORCC) in White City, Oregon. Testing must comply with NFPA 110, specifically section 8.4.2.3. Each EPS unit must be exercised with supplemental loads at no less than 50% of its nameplate kW rating for 30 continuous minutes, then at no less than 75% for 1 continuous hour, totaling at least 1.5 hours per unit. The work is performance-based, with no specified budget or non-bid timelines mentioned.

Department/Ind.Agency Subtier Office
VETERANS AFFAIRS, DEPARTMENT OF VETERANS AFFAIRS, DEPARTMENT OF 260-NETWORK CONTRACT OFFICE 20 (36C260)
  PSC   H228 EQUIPMENT AND MATERIALS TESTING- ENGINES, TURBINES, AND COMPONENTS
LOCATION: White City VA Medical Cetner VA Southern Oregon Rehabilitation Center
Primary Contact
Michael Allred
509-***-1906

Links (0)

Attachments (1)


Data sourced from SAM.gov. View Official Posting »

White City VAMC - Diesel powered generator maintenance

Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14)
Notice ID:36C26026Q0706

The contractor will provide generator maintenance for the White City VAMC in Oregon, specifically at the VA Southern Oregon Rehabilitation Center and Clinics. The contract includes a 1-year base period and four 1-year option periods. Services involve testing and exercising four diesel-powered emergency power supply systems in accordance with NFPA 110. Testing requires supplemental loads at not less than 50% of nameplate rating for 30 minutes and 75% for 1 hour, for a total of at least 1.5 continuous hours.

Department/Ind.Agency Subtier Office
VETERANS AFFAIRS, DEPARTMENT OF VETERANS AFFAIRS, DEPARTMENT OF 260-NETWORK CONTRACT OFFICE 20 (36C260)
  PSC   H228 EQUIPMENT AND MATERIALS TESTING- ENGINES, TURBINES, AND COMPONENTS
LOCATION: Not Given
Primary Contact
Michael Allred
509-***-1906