Technicians shall perform inspection, tuning, testing, calibrating, and adjustments of burners and boilerplant controls as specified below on #1, #2, and #3 boiler and auxiliary control devices. This ...
Technicians shall perform inspection, tuning, testing, calibrating, and adjustments of burners and boilerplant controls as specified below on #1, #2, and #3 boiler and auxiliary control devices. This shall be done in accordance with a schedule provided by VAMC Spokane. Boiler tuning and calibration shall be completed every October on the 350 hp boilers and every march on the 200 hp boilers. Auxiliary devices, and mainstream flow transmitters shell be calibrated annually. Subtitle .............. 2X 350 HP Boiler Manufacturer........... Burnham Boiler Type............ Fire tube Boiler Year Built............. 2020 Design Pressure........ 200.00 PSI Operating Pressure..... 120.00 PSI [relief valve set pressure] Design Temperature..... 650.00 degrees Fahrenheit Rated Capacity . 12,000 pounds per hour Fuel Natural gas and or #2 fuel oil fired boilers Subtitle .............. 2X 200 HP Boiler Manufacturer........... Burnham Boiler Type............ Fire tube Boiler Year Built............. 2020 Design Pressure........ 200.00 PSI Operating Pressure..... 120.00 PSI [relief valve set pressure] Design Temperature..... 650.00 degrees Fahrenheit Rated Capacity . 6900 pounds per hour Fuel Natural gas and or #2 fuel oil fired boilers