The purpose of this amendment is to add the below boiler specifications to the Statement of Work. Manufacturer Johnston Manufacturer Model Number 509 series Confirm Water Tube design 3 Pass wetback Fi...
The purpose of this amendment is to add the below boiler specifications to the Statement of Work. Manufacturer Johnston Manufacturer Model Number 509 series Confirm Water Tube design 3 Pass wetback Firetube Boiler Maximum Allowable Operating Pressure MAWP 200 psig Boiler Capacity lb steam per hour / pressure / temperature (if not saturated) 6900 lbph / 110 psig / 350 degf. Manway dimensions Burner Side manhole 15 x11 / Back side manhole 15 dia. Availability (inspect all 3 on one trip, one trip per boiler, or rotate boilers out of service keeping one on line) rotate boilers out of service keeping two on line Confirm that Grand Junction VAMC will provide hole-watch NO, Contractor will provide all manpower and equipment along with their own confined space plan. VA will review and accept or deny plan prior to entry.