PRE-BID QUESTIONS FOR PROJECT 657A4-17-901 REPLACE LIFE SAFETY GENERATOR Please confirm the General Contractor is to provide the commissioning agent and NOT the VA. The Contractor Provides Commissioni...
PRE-BID QUESTIONS FOR PROJECT 657A4-17-901 REPLACE LIFE SAFETY GENERATOR Please confirm the General Contractor is to provide the commissioning agent and NOT the VA. The Contractor Provides Commissioning, see Cx specification section. Can the Superintendent act as the QC and SSHO? No, the SSHO and Superintendent shall be separate individuals. The SSHO can act as QC; the Superintendent cannot act as QC. Please provide drawings and details for the pre-engineered metal buildings. This is manufacturer specific and the plans detail a general space/functional requirement. The Metal Enclosed Switchgear will have to be ordered through the submittal process. There are no detailed drawings as variations exist between manufacturers. Please provide the site visit sign-in sheet. CO shall provide What is the size of the diesel tank? The generator manufacturer shall size the tank for required sizing to facilitate fuel storage for run times of 96+ hours. The tank is dependent of fuel burn rate of the generator. The tank shall be sized per NFPA 99, 101, 110. How old is the fuel in the tank? The fuel is not stagnant; we regularly operate the generator. The fuel shall be retuned (filtered transferred) to the VA. We keep a minimum quantity to support required run times. Has the fuel been treated yearly for summer and winter? No, the diesel is not treated.