The purpose of this amendment is to post the answers to questions received during the solicitation process. Is BAC OEM Fill Media required? (Please note, in order to guarantee thermal capacity OEM Fi...
The purpose of this amendment is to post the answers to questions received during the solicitation process. Is BAC OEM Fill Media required? (Please note, in order to guarantee thermal capacity OEM Fill media is recommended. Aftermarket Block-style fill media will have an approximate 5% de-rate in performance when compared to BAC OEM fill media.) The Cooling Tower is at the limit of its capacity. A 5% loss of capacity would be a major problem. Therefore, we will need to use BAC Fill media which would not create a loss in capacity. Will we be able to drop ship the parts at the worksite or are we going to have to have them delivered at time of repair? Delivered at time of repair. Is compressed air available for power tools and water outlet in the event that a pressure washer may be useful? No compressed air near the job site. Water is available. ALL OTHER TERMS AND CONDITIONS REMAIN UNCHANGED!