Y1DA--630A4-26-401 MRI AHU Modification
The VA’s response addresses a substitution request for hallway fan coil units as part of an MRI AHU modification. Option A—six ceiling-mounted 18,000 BTU/h fan coil units—would be acceptable provided there is no additional cost to the VA, though these units cannot be equally spaced due to ceiling constraints. Option B, using three higher-capacity ceiling-mounted units spaced evenly, is also described as an alternative but is not explicitly approved. The VA notes that wall-mounted units need at least 6 inches of ceiling clearance, leaving about 76 inches of headroom in an 8-foot corridor. No budget amounts, submission timelines, or specific performance location are stated beyond the corridor/hallway setting.