36C24222Q0367 Questions Responses from the Contracting Specialist are in red font Can a walk-through be scheduled to see access and required cabling needs? A site visit will not be conducted for this ...
36C24222Q0367 Questions Responses from the Contracting Specialist are in red font Can a walk-through be scheduled to see access and required cabling needs? A site visit will not be conducted for this solicitation. Castle Point Building 7: Generator type and rating unknown. Generator is Onan 300kw. Montrose Building 16 and 18: Generator rating missing. There is no generator for building 18 specifically. Building 16 s generator is currently out of service. It was a 300kw Onan. Are generators located inside? What is the furthest distance from the generator to outside of the building? Castle Point: Most generators are located in buildings. Load bank equipment will not be inside the building. There is enough room to get next to the generator buildings and properly connect the load bank. Montrose: Most generators are located outside at the FDR Campus (Montrose), some are in buildings. There is enough room to get the load bank equipment near the outdoor generators as well as the generators that are in buildings to properly connect the equipment.