The purpose of this amendment is to provide answers to questions asked by vendors for solicitation number 36C24221Q0064. See questions/answers below: What are the rolling door sizes of the receiving d...
The purpose of this amendment is to provide answers to questions asked by vendors for solicitation number 36C24221Q0064. See questions/answers below: What are the rolling door sizes of the receiving doors in case they are overhead rolling fire doors? There are no rolling fire doors in our chutes; the receiving doors 18 x18 hinged with closures and a mag lock, the emptying doors in the SB are 26 x32 hinged at the top and held open with chain and fusible link. Please clarify on the reference to the chute receiving doors and what they are used for (i.e. where the garbage and laundry chutes empty out, etc.)? There are 11 chute receiving doors on each wing from 10th floor to Subbasement, A, B, and D wings are used for laundry, C wing is for garbage, the chutes empty into the SB Please provide quantities and sizes of all horizontal fire doors and swinging fire doors? This will be addressed at the mandatory site visit on 11/5/2020 and publicized as an amendment to this solicitation afterwards, if necessary. Please provide the Life Safety Drawings See attachment Drawings Combined PDF All other terms and conditions remain the same.