Amendment 0001 - Questions and Answers: 1. The heating oil tanks are specified as "Flameshield" tanks. Would a STI-F921 tank be acceptable? Yes 2. Our standard stock skid design is attached? Would tha...
Amendment 0001 - Questions and Answers: 1. The heating oil tanks are specified as "Flameshield" tanks. Would a STI-F921 tank be acceptable? Yes 2. Our standard stock skid design is attached? Would that be acceptable? Yes, your stock skid would be acceptable. 3. You specified a "Fireguard" tank but mentioned STI-F921, would you like me to disregard that reference? Yes 4. Your avgas tank photo shows a tank with a manhole, do you want a manhole with this size tank? No, a manhole is not required for this size tank. 5. Our standard spill basin is 7-1/2 gallons, you specified minimum 7 gallons. Is our standard basin okay? Yes 6. We are proposing standard emergency vents without a vacuum vent. Is that acceptable? Yes