Generator Fuel Handling System-Value Engineered-Revision-2. Provide and install a compltet and working system for the supply of necessary fuel and the return of excess diesel fuel from each (2) 1500 K...
Generator Fuel Handling System-Value Engineered-Revision-2. Provide and install a compltet and working system for the supply of necessary fuel and the return of excess diesel fuel from each (2) 1500 KW generator day(belly) tanks to the primary 8000 gallon tank. System to include: (2) 17 GPM Self Priming return pumps, 120V (2) Pump Control Panels (2) Audible/Visual alarm modules (2) Suction pipes with re-usuable particulate screens (2) 3-Position tank level switches (2) Check Valves (3) Isolation Valves All components necessary for new 1-1/4" return line All Electrical power connections to facility Power and connections to facility power Power and control conduits as needed (100' allowance for control conduits to security system All required signage/labelling of conduits and piping Engineered drawing Housekeeping pads for pumps and/or controllers Containment vessels for leaks and spills around pumps Exclusions/Conditions Free-standing pipe/conduit supports by others Eletrical power available with 50' of generators Control wiring eternal to controllers by others( functionally drawing provided)