FY24 Emergency Replace Condensers FS Warehouse MOD 00001 Recover refrigerant, disconnect piping, move equipment with customer forklift, set new equipment, connect to existing piping, install new sucti...
FY24 Emergency Replace Condensers FS Warehouse MOD 00001 Recover refrigerant, disconnect piping, move equipment with customer forklift, set new equipment, connect to existing piping, install new suction line accumulator outside new unit, pressure test, evacuate lines, charge with new refrigerant, start and test. Isolated compressor and pressure tested with customer supplied nitrogen. Traced to leak at base of compressor bolt. Attempted to tighten to repair. Found unsuccessful. Determined compressor would need to be removed for repair or possibly sent out for rebuild. Unit is 15 years old, added customer supplied POE to prevent oil failure, reset from tripping. Released nitrogen charge and completed evacuation test. Restored power, unit is operational but continuously loosing oil. Customer requests replacement unit.