SAFETY SHOWER
The opportunity is for a skid-mounted, pneumatic emergency safety shower and eyewash station designed for Class I Division 2 hazardous locations, with self-contained operation where no potable water source exists. It must meet ANSI/ISEA Z358.1-2014, delivering at least 15 minutes of tepid water from an insulated 325-gallon tank, with an immersion heater and heat tracing for operation down to 0°F. A pneumatic pump (60-120 PSI) ensures spark-free operation and backup during outages, supplying at least 20 GPM for the shower and 0.4 GPM for the eyewash. The unit must be built on a corrosion-resistant steel skid with stainless steel piping, a pull-handle activation, and powered by 120V single-phase 60Hz (20-amp).