Notice ID:W911RP-20-Q-HVAC
AMENDMENT 0002 - The purpose of amendment 0002 is to address a contractor's questions as follows: QUESTION: Does the customer need any of the following: 1. Standard Rigid Factory Curb to sit on? RESPO...
AMENDMENT 0002 - The purpose of amendment 0002 is to address a contractor's questions as follows: QUESTION: Does the customer need any of the following: 1. Standard Rigid Factory Curb to sit on? RESPONSE: No factory curb is required, as long as the unit has horizontal discharge. 2. We are only hitting 60F Leaving Air Temperature. Do they need to get lower to dehumidify? RESPONSE: They do not need to get lower than 60F Leaving Air Temperature. 3. What type of BACnet interface do they need? RESPONSE: The fresh air unit needs a BACnet unit controller that is supported by Tracer SC. 4. What is the entering air temperature for heating? RESPONSE: No defined entering air temperature for heating. Just the 32kW heating capacity. 5. I see that this project is in AR, are there any other special conditions we need to know? Does this job have a Military Priority Rating? RSEPONSE: This requirement is rated DO-A6. =========================================================================== AMENDMENT 0001 - REVISION: PINE BLUFF ARSENAL PROVIDED CLARIFICATION ON THE REQUIREMENT AND THE FOLLOWING IS ACCEPTABLE: 100% OSA Unit requirements: 95F ambient condensing temperature, 3000 CFM airflow, 78.8F entering wet bulb, and 90.1F entering dry bulb Due to formatting issues, the combined synopsis/solicitation for the HVAC and Humidifer requirement to support Pine Bluff Arsenal, is provided as an attachment. Also attached is Addendum information that is applicable to this procurement. For questions/issues, please contract Sheila Peters, email address sheila.k.peters2.civ@mail.mil.