Inactive
Notice ID:W90VN724RA014-0002
Notice to Offerors. Q& A for the solicitation, W90VN724RA014_ Repair Flying Squadron Facility, B-2834 Regarding the Clarification for the scope of work of the fire alarm system. - Question: Please che...
Notice to Offerors. Q& A for the solicitation, W90VN724RA014_ Repair Flying Squadron Facility, B-2834 Regarding the Clarification for the scope of work of the fire alarm system. - Question: Please check if the FA control panel should be installed additionally in the SCIF area on the 2nd floor. - Answer: According to chapter 11, section G of the IC Technical Specification for Construction and Management of SCIF v151, there is no need to install a separate FACP in the SCIF area. (see attached Pages from IC_Technical_Specifications_for_Construction_and_Management_of_Sensitive_Compartmented_Information_Facilities_v151) ************************************************************************************************************** (WP MATOC) AMENDMENT OF SOLICITATION_ W90VN724RA014-0002, Repair Flying Squadron Facility, B-2834, Kunsan AB. - The purpose of this amendment is to update the SOW (Statement of Work) according to questions and answers after Site Orientation (see attached SOW for more details). - All other terms and conditions of this solicitation remains unchanged.