The Current High-Density system for Sterile Processing Area Needs to be replaced Due to the sterile environment, an ICRA must be constructed to mitigate the risk of dust and debris causing contaminati...
The Current High-Density system for Sterile Processing Area Needs to be replaced Due to the sterile environment, an ICRA must be constructed to mitigate the risk of dust and debris causing contamination to the current environment. This process will include: 1) Construction will consist of metal studs and 6 mil fire retardant poly with an ingress and egress Anteroom. 2) The ICRA will have 2 negative air machines that will run all the time to obtain and maintain negative pressure. 3) The pressure must be continually measured with a recording type manometer 4) The ICRA will be constructed for both halves of the storage system replacement work and when done, the ICRA will be removed and equipment retrieved. 5) Pre-filters for the negative air machines must be provided. 6) Sticky Matts for containment must be provided.