Inactive
Notice ID:F3NT112139AW01
4 EA Recommended Model/Part number: Air Rover Model: RULCR60CA-15KW COOLING Total Cooling Capacity: 68,400 BTU/HR Maximum Ambient Temperature: +150°F Minimum Ambient Temperature: +50°F Design Return A...
4 EA Recommended Model/Part number: Air Rover Model: RULCR60CA-15KW COOLING Total Cooling Capacity: 68,400 BTU/HR Maximum Ambient Temperature: +150°F Minimum Ambient Temperature: +50°F Design Return Air Dry Bulb Temperature: 90°F Design Return Air Relative Humidity: 50% Max Approximate Supply Airflow Rate: 2300 CFM HEATING Total Heating Capacity: 51,180 BTU/HR Heat Source(s) Electric Heaters Minimum Ambient Temperature: 50°F PHYSICAL DIMENSIONS Height: 46.00” (approximate with skid) Width: 34” Depth: 45.00” (overall including ducts) The unit must have the same dimensions in order for it to fit inside the HEMP boxes. The supply air and return air ducts are 18” in diameter. These must align in order for a metal slide to cover the ducts and minimize air loss. The condenser fan must exit through the top and also align perfectly for a metal slide to direct the air out of the box. The condenser coils are on both sides of the unit and have metal boxes with waveguides built in that must also align in order for the air to flow in. Any variation in alignment will cause the unit to malfunction with loss of air flow and overheating problems. POWER REQUIREMENTS Voltage: 208 Volts Tolerance Recommended ±10% Number of Phases: 3 Phase Frequency: 60 Hz Maximum Power Draw: 11.6 kW (Cooling) 15 kW (Heating)